How many square meters of natural gas are needed for ten tons of boiler, that is, to calculate the gas consumption of natural gas boiler. The formula for calculating gas consumption of natural gas boilers is: power*time/fuel calorific value/utilization ratio of calorific value of natural gas boilers. Assuming that the calorific value of natural gas fuel is 36.22MJ/Nm3 and the thermal efficiency of natural gas is 92%, it can be concluded that a 10 ton gas boiler need 750 cubic meters of natural gas per hour, and the 24-hour natural gas consumption of boilers is 18,000 cubic meters.
Selection of 10 ton natural gas boiler (steam boiler):
1. 10 ton WNS gas boiler: rated steam pressure 0.7-1.6 mpa, rated steam temperature 170-204℃, feed water temperature 104℃, natural gas boiler size 6290*2640*3178 mm;
2. 10 tons SZS gas saturated boiler: rated steam pressure 1.25 mpa, rated steam temperature 194℃, feed water temperature 104℃, natural gas boiler size 7200*3280*3307 mm;
3. 10 tons of SZS gas superheated steam boiler: rated steam pressure 1.25 mpa, rated steam temperature 350℃, feed water temperature 104℃, natural gas boiler size 7200*3280*3307, maximum transport weight 29 tons.